modbus_read_input_registers
Name
modbus_read_input_registers - read many input registers
Synopsis
Description
The modbus_read_input_registers() function shall read the content of the nb
input registers to address addr
of the remote device. The result of the
reading is stored in dest
array as word values (16 bits).
You must take care to allocate enough memory to store the results in dest
(at
least nb * sizeof(uint16_t)
).
The function uses the Modbus function code 0x04 (read input registers). The holding registers and input registers have different historical meaning, but nowadays it's more common to use holding registers only.
Return value
The function shall return the number of read input registers if successful. Otherwise it shall return -1 and set errno.
Errors
- EMBMDATA, too many bits requested.